The horizontal flow, lateral access SAH System provides efficient air purification mediums with flows ranging from 425 to 67,920, m3/h.

This equipment is made of an aluminium structure with epoxy painted steel panels or of stainless steel. They have two module beds to deliver the maximum protection against all sorts of gasses and also provide protection against particles with a G4 type pre-filter and an F7 type filter. These systems may include a fan.

This equipment can be loaded with different quantities depending on the needs for each use.

To load the granulates in the SAH Filtration systems Bioconservacion provides two types of modules:

  • PP12
  • PP18

Using one or the other is determined on the basis of client needs related to efficacy, autonomy, and load-consumption.

Within the SAH range there are two options:

  • SAH12 machines (with PP12 module)

Generally designed with residency periods of between 0.12 to 0.23 seconds with frontal air speeds between 0.64 and 1.27 m/s speed and air flows between 425 to 33,980 m3/h. Usually this sort of machine is used in industrial applications.

  • SAH18 machines (with PP18 modules)

These are generally designed with residency times between 0.03 and 0.06 seconds with frontal air speeds between 1.27 and 2.55 m/s and air flows from 425 to 67.920 m3/h. Usually, this sort of machine is used in commercial applications.